The size on a tank, 40 or 50 gallons, is not the number that decides whether the last shower of the morning runs cold. For a tank it is the first hour rating; for a tankless heater it is the flow it can heat at your water temperature.

Uppdaterad 19 november 2026

Kort svar

For a tank, add up the hot water your household uses in its busiest hour: a family of four with three showers, a shave and dishes by hand needs about 65 gallons (246 L), so buy a heater with a first hour rating of at least 65. For a tankless heater, one shower plus one tap is 3.25 gpm (12.3 L/min) and needs about 114,000 BTU/h (33 kW) with 50 °F inlet water.

Beräkna

Kalkylator för varmvattenberedare

Se hur mycket varmvatten en beredare med tank behöver kunna ge första timmen eller vilket flöde och vilken effekt en genomströmningsberedare behöver för ditt hushåll.

Kalkylator för varmvattenberedare →

Hot water per use

The US Department of Energy sizes a storage or heat pump water heater on peak hour demand: the hot water used in the busiest hour of a normal day. These are the amounts its worksheet counts for each use.

Hot water per use (U.S. DOE worksheet)
UseGallonsLitres
Shower2076
Shaving28
Washing dishes by hand or food prep311
Automatic dishwasher726
Top-loading clothes washer2595
Front-loading clothes washer1557

Think about when your household actually overlaps. For most families it is the morning, when everyone showers before work and school. For others it is the evening, when the washer and dishwasher run while someone is in the shower.

Peak hour demand for typical households

Add the uses that happen in the same hour. The total is the minimum first hour rating (FHR) to look for on the yellow EnergyGuide label or in the data sheet.

Busiest hour and first hour rating to buy
Household and busiest hourSumFHR at least
One person: shower and dishwasher20 + 727 gal (102 L)
Couple: two showers, a shave, dishes by hand40 + 2 + 345 gal (170 L)
Family of four: three showers, a shave, dishes by hand60 + 2 + 365 gal (246 L)
Family of five, evening: three showers, dishwasher, top-loading washer60 + 7 + 2592 gal (348 L)

The last row shows how much one appliance matters: swap the top-loader for a front-loader and the same evening needs 82 gallons, not 92. Moving the laundry to another hour takes 25 gallons off the peak entirely.

First hour rating is not tank size

The first hour rating is how much hot water the heater delivers in one hour starting with a full tank. It includes what the burner, element or heat pump heats during that hour, so two heaters with the same tank can have different ratings: the faster one reheats, the more it delivers.

That is why the DOE tells you to compare the rating with your peak demand and not the gallons printed on the side. Two 50-gallon tanks can differ a lot.

Tankless: flow and temperature rise

A tankless heater has no store, so it must heat the water as fast as you draw it. Its size is a flow rate at a temperature rise. The DOE method: add the flow of the outlets you use at the same time, then find the rise from your incoming water to about 120 °F (49 °C). If you do not know your inlet temperature, use 50 °F (10 °C); the rise is then 70 °F (39 °C).

The DOE uses 2.5 gallons per minute for a shower and 0.75 gpm for a faucet as examples. Heating water takes about 500 BTU per hour for each gpm and each degree Fahrenheit of rise, from the weight of water (62.4 lb per cubic foot at 50 °F, U.S. Geological Survey) and one BTU per pound per degree.

Power a tankless heater needs for a 70 °F (39 °C) rise
Used at onceFlowPower
One shower2.5 gpm (9.5 L/min)87,600 BTU/h (25.7 kW)
Shower and a kitchen tap3.25 gpm (12.3 L/min)114,000 BTU/h (33.4 kW)
Two showers5 gpm (18.9 L/min)175,000 BTU/h (51.3 kW)

The DOE notes that gas tankless units reach a 70 °F rise at about 5 gpm, electric ones at about 2 gpm. In practice that means a whole-house electric tankless heater suits one shower at a time; a family that runs two showers together needs gas, two units or a tank.

Worked example: family of four, morning rush

Between 6:30 and 7:30 three people shower, one shaves and breakfast dishes are washed by hand: 60 + 2 + 3 = 65 gallons.

Tank: look for a first hour rating of at least 65 gallons (246 L) on the EnergyGuide label or data sheet. Compare models by that rating, not by tank size.

Tankless: the showers are one after another, but someone runs the kitchen tap during a shower, so the peak flow is 3.25 gpm. With 50 °F inlet water that needs about 114,000 BTU/h, which is a gas unit; an electric one would need over 33 kW.

Mistakes that leave you with cold showers

Undersized water heaters almost always come from one of these four shortcuts.

  • Buying by tank volume and ignoring the first hour rating.
  • Counting average daily use instead of the busiest hour.
  • Sizing a tankless heater for the summer inlet temperature. In winter the incoming water is colder and the rise larger.
  • Expecting an electric tankless heater on a normal household supply to serve two showers at once.

Frågor

What size water heater for a family of 4?

Count their busiest hour. Three showers, a shave and dishes by hand come to 65 gallons (246 L), so choose a first hour rating of at least 65 gallons.

Is a 40 gallon water heater enough for 4 people?

It is if its first hour rating covers your busiest hour, about 65 gallons for three showers, a shave and dishes. The tank size alone does not tell you; read the first hour rating on the label.

How many gallons of hot water does a shower use?

The DOE worksheet counts 20 gallons (76 L) per shower.

What size tankless water heater do I need for a 3 bathroom house?

Size it for the showers that run at the same time, not the number of bathrooms. Two showers at 2.5 gpm with a 70 °F rise need about 175,000 BTU/h (51 kW), which is gas territory.

What temperature rise should I use?

The difference between your incoming water and about 120 °F (49 °C). Without a measurement, the DOE suggests 50 °F (10 °C) incoming water, a 70 °F (39 °C) rise.

Beräkna

Kalkylator för varmvattenberedare

Se hur mycket varmvatten en beredare med tank behöver kunna ge första timmen eller vilket flöde och vilken effekt en genomströmningsberedare behöver för ditt hushåll.

Kalkylator för varmvattenberedare →

Källor

  1. [1]Sizing a New Water Heater. U.S. Department of Energy, Energy Saver. Storage and heat pump water heaters: choose a first hour rating at least equal to the peak hour demand. Gallons per use: shower 20, shaving 2, hand dishwashing or food prep 3, automatic dishwasher 7, top-loading clothes washer 25, front-loading (H-axis) 15. Tankless: add the flow rates of devices used at once (example 0.75 gpm faucet, 2.5 gpm shower); incoming water 50 °F (10 °C) unless known; 120 °F (49 °C) for most uses; gas units reach a 70 °F rise at 5 gpm, electric at 2 gpm. Kontrollerat 18 november 2026
  2. [2]Water Density (Water Science School). U.S. Geological Survey. Water at 50 °F (10 °C) weighs 62.408 lb/ft³ (0.99975 g/cm³); with 1 Btu per lb per °F this gives the heat to warm a flow of water. Kontrollerat 18 november 2026