Wire size calculator
Pick the copper cable size for a circuit from the load current, the length and the voltage drop you allow. Metric uses the DIN VDE 0298-4 current table; imperial uses NEC Table 310.16.
Circuit
Copper conductors, 30 °C ambient, not more than three current-carrying conductors. Ampacity after NEC Table 310.16, limits of 240.4(D).
Load
From the appliance label, or the breaker rating for a general circuit.
Cable run
From the panel to the last outlet, along the route the cable takes.
The NEC suggests 3 % for a branch circuit and 5 % for feeder and branch together.
Add this calculator to your website
Free for any website: paste this code where the calculator should appear. It keeps itself up to date, fits its height to the content and links back to the full page with the explanations.
How to use it
- 01Pick the supply: single-phase for ordinary sockets and lights, three-phase for a cooktop, a heat pump or a wallbox wired that way.
- 02Enter the load current from the appliance label, or the power in watts. For a general socket circuit use the breaker rating.
- 03Enter the cable length one way, from the panel to the farthest outlet along the real route, and the voltage drop you allow.
- 04In metric, pick how the cable is laid. In imperial, pick the cable type and say whether the load runs for three hours or more. Read the smallest size that passes both checks.
How it is calculated
A cable has to pass two checks. It must carry the current without overheating, and the voltage lost along it must stay small enough for the appliance at the far end. The calculator takes the smallest size that passes both.
- Current from power
- I = P / (U × cos φ), three-phase I = P / (√3 × U × cos φ)
- Current check (metric)
- Ib ≤ In ≤ Iz
- Current check (NEC)
- I × 1.25 (continuous) ≤ ampacity
- Voltage drop, single-phase
- ΔU = 2 × L × I × R
- Voltage drop, three-phase
- ΔU = √3 × L × I × R
- Resistance when warm
- R(t) = R20 × (1 + 0.00393 × (t − 20))
Metric: the current a cable may carry, Iz, comes from the DIN VDE 0298-4 table reproduced by ABB for copper with PVC insulation at 30 °C. It depends on how the cable is laid (A1 to E) and on the number of loaded conductors: two for single-phase, three for three-phase. The breaker In has to lie between the load current Ib and Iz.
Imperial: the ampacity comes from NEC Table 310.16 for copper. NM-B and UF-B cable is read in the 60 °C column. Under 240.4(D) the breaker on 14, 12 and 10 AWG copper may not exceed 15, 20 and 30 A. A continuous load, one that runs for three hours or more, is sized at 125 %.
For the drop the metric side uses the IEC 60228 resistance at 20 °C, raised to 70 °C, the highest temperature PVC insulation is made for. That is on the safe side: at 30 °C the formula gives the 34 m that ABB lists for 1.5 mm² at 16 A and 400 V. The imperial side uses the 75 °C resistances of NEC Chapter 9, Table 8.
The calculator does not apply corrections for bundled cables, hot rooms or thermal insulation around the cable. These lower the current a cable may carry and are applied by the electrician.
Worked example
A 16 A socket circuit, 20 m, 230 V, cable in conduit on the wall (B2)
- Current check: 1.5 mm² carries 16.5 A in method B2 with two loaded conductors, so 16 A fits.
- Drop on 1.5 mm²: 2 × 20 m × 16 A × 12.1 Ω/km × 1.197 = 9.3 V, that is 4.0 %. Too much.
- Drop on 2.5 mm²: 2 × 20 × 16 × 7.41 × 1.197 / 1000 = 5.7 V, that is 2.5 %. Size: 2.5 mm².
- Imperial: 16 A at 120 V over 100 ft of NM-B. 12 AWG carries it, but drops 5.1 %; 10 AWG drops 3.2 %; 8 AWG drops 2.1 % and is the size to buy.
Getting the order right
Measure the real route
Cables go up walls, along ceilings and around doors. Measure along that path; a straight line on the plan can be half the real length.
Long runs need a bigger cable, not a bigger breaker
When the drop decides the size, the breaker stays the same. A larger breaker on a thin cable is the one thing the rules forbid.
Count the start-up of motors
Pumps, compressors and saws draw several times their rated current for a moment. A cable sized right at the drop limit can make them stall at the far end of a long run.
Common mistakes
- Entering the length there and back. Enter it one way; the formula already counts both conductors.
- Reading the 75 °C column for NM-B cable. NM-B is sized in the 60 °C column.
- Putting a 20 A breaker on 14 AWG because the 75 °C column says 20 A. Under 240.4(D) 14 AWG copper is limited to 15 A.
- Ignoring cables run together or through insulation. Bundling and heat lower the rating, and the electrician has to correct for them.
Questions
What size wire for a 20 amp circuit?
12 AWG copper, because 240.4(D) limits 14 AWG to 15 A. On a long run the voltage drop can push it to 10 AWG: at 16 A and 120 V, 12 AWG stays under 3 % up to about 58 ft.
What cable size for 16 A?
In conduit on a wall (B2) 1.5 mm² carries 16.5 A, so it is enough for short runs. At 230 V it stays within 3 % up to about 14 m when the cable is warm; beyond that use 2.5 mm².
Why does the length change the size?
Every metre of copper has resistance, so a long cable loses voltage. The rules in Germany allow 3 % from the meter, and the NEC suggests 3 % for a branch circuit. A thicker cable has less resistance and loses less.
Why is my result larger than in other calculators?
We take the cable resistance at 70 °C, the highest temperature PVC cable is made for. Tables that use 20 °C or 30 °C allow somewhat longer runs.
Can I wire the circuit myself?
That depends on where you live. In Germany, the UK and many other countries the connection to the mains must be made by a licensed electrician. Use the result to plan and to talk to them.
Guides on this topic
- Wire size for long runs: current rating and voltage drop
How to choose copper wire size by current and by voltage drop: NEC ampacity and the 3 % rule, DIN VDE 0298-4 in metric, with worked examples for 120 V and 230 V.
Related calculators
Sources
- [1]Kabel- und Leitungsdimensionierung (2CDC400027D0104 Rev. E, 2023-10), after DIN VDE 0298-4 and DIN VDE 0100-430. ABB Stotz-Kontakt. Table 2: current-carrying capacity Iz of copper PVC cables at 30 °C ambient for installation methods A1, A2, B1, B2, C and E, two or three loaded conductors, 1.5 to 50 mm². Rule Ib ≤ In ≤ Iz. 3 % voltage drop behind the meter (DIN 18015-1); Table 11 (1.5 mm², 16 A, 400 V: 34 m at 3 %) as a check of the drop formula.. Checked November 10, 2026
- [2]Conductor resistance (IEC 60228 / DIN EN 60228, class 1 and 2). Bayka. Maximum DC resistance of plain copper conductors at 20 °C: 12.1 Ω/km for 1.5 mm² down to 0.387 Ω/km for 50 mm².. Checked November 10, 2026
- [3]Conductor resistance (temperature correction after IEC 60228 Annex B). Electrical Cable Engineering. R(t) = R20 × (1 + 0.00393 × (t − 20)) for annealed copper.. Checked November 10, 2026
- [4]Ampacity chart (NEC Table 310.16, copper, not more than three current-carrying conductors, 30 °C ambient). Cerrowire. Allowable ampacity of copper conductors 14 AWG to 1/0 AWG in the 60 °C and 75 °C columns.. Checked November 10, 2026
- [5]NEC Chapter 9, Table 8: Conductor Properties. NFPA (copy hosted by NECA-IBEW Electricians). DC resistance of uncoated copper at 75 °C in Ω per 1,000 ft: 14 AWG 3.07 (solid) to 1/0 AWG 0.122.. Checked November 10, 2026
- [6]National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (L. Mari, 2022-06-07). EEPower. NEC 240.4(D): overcurrent protection of copper conductors not more than 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG. 210.19(A)(1): conductors carry the noncontinuous load plus 125 % of the continuous load. 110.14(C): 60 °C column for equipment rated 100 A or less unless marked for 75 °C.. Checked November 10, 2026
- [7]Voltage Drop Limitations on Branch Circuits (M. Holt, 2015-05-05). EC&M. NEC 210.19(A) Informational Note No. 4: not more than 3 % on the branch circuit and 5 % for feeder and branch circuit together.. Checked November 10, 2026