Electrical load calculator
Find the electrical load of a house and the service size it needs, after the optional method of the US National Electrical Code.
Your house
Enter the size of the house and its large electric appliances. You get the total load and the main breaker size (service size) the house needs.
Floor area and circuits
By outside dimensions; leave out open porches, the garage and unfinished space.
Service voltage
20 A kitchen and dining circuits; at least 2, 1,500 VA each.
Usually 1, 1,500 VA.
Fixed appliances
Everything fastened in place or on its own circuit: range, oven, dryer, water heater, dishwasher, disposal, well pump, EV charger. Enter the rating on the nameplate in VA (watts).
Heating and cooling
Nameplate ratings. Only the largest of air conditioning, heat pump and electric heating counts, because they do not run at full load together.
Separately controlled heaters: 3 or fewer count at 65 %, 4 or more at 40 %.
Add this calculator to your website
Free for any website: paste this code where the calculator should appear. It keeps itself up to date, fits its height to the content and links back to the full page with the explanations.
Cómo usarla
- 01Enter the living area of the house, measured by its outside walls.
- 02Keep two kitchen circuits and one laundry circuit unless you have more.
- 03Add every fixed appliance with the rating from its nameplate: range, dryer, water heater, dishwasher, EV charger.
- 04Enter the air conditioning, heat pump or electric heating ratings.
- 05Read the calculated load in amps and the standard service size to plan for.
Cómo se calcula
The calculator follows the optional method for dwellings in section 220.82 of the US National Electrical Code (2020 edition), as explained by Mike Holt in EC&M and used on permit worksheets such as the City of Bellevue form.
- Connected load
- L = 3 VA × ft² + 1,500 VA × circuits + appliances
- Demand
- D = 10,000 + 40 % × (L − 10,000)
- Total
- T = D + largest heating or cooling load
- Amperes
- I = T / 240 V (or 208 V)
General lighting and receptacles count at 3 VA per square foot of living area by outside dimensions; open porches, garages and unfinished space are left out. Each kitchen small-appliance circuit and each laundry circuit counts 1,500 VA. Fixed appliances count at their nameplate rating.
Not everything runs at once, so only the first 10 kVA of that load counts in full and the rest at 40 %.
Heating and cooling are added separately, taking only the largest: air conditioning at 100 %, a heat pump at 100 % plus 65 % of its backup heat, or electric space heating at 65 % (three or fewer separately controlled units) or 40 % (four or more).
The service is the next standard rating at or above the load, at least 100 A, because the method only applies to services of 100 A and more.
Other countries size house supplies differently, for example by a diversity table of the network operator. Use the result as a US planning figure.
Ejemplo resuelto
A 2,000 ft² house with a dryer, range and central air
- Lighting: 2,000 × 3 = 6,000 VA; 2 kitchen and 1 laundry circuit: 4,500 VA.
- Appliances: dryer 5,000 VA, range 12,000 VA, water heater 4,500 VA: 21,500 VA.
- Connected load 32,000 VA: 10,000 + 40 % × 22,000 = 18,800 VA.
- Central air 5,000 VA: total 23,800 VA, which is 99.2 A at 240 V.
- Service: 100 A.
Para acertar con el pedido
Read the nameplate
The rating is on a label inside the door or on the back of the appliance, in watts, VA, or volts and amps (multiply them).
Plan for what is coming
An EV charger, a heat pump or an induction range can push a 100 A service over. Add them now if you plan them.
Count heating or cooling once
Only the larger of the two is added, because a house does not heat and cool at full load at the same time.
Let the electrician confirm
Local amendments and the utility may ask for more. The permit worksheet is the final word.
Errores frecuentes
- Adding heating and air conditioning together.
- Counting the garage and porches in the floor area.
- Using the breaker size of an appliance instead of its nameplate rating.
- Forgetting the two kitchen circuits and the laundry circuit.
Preguntas
How do I calculate the electrical load of my house?
Add 3 VA per square foot, 1,500 VA for each kitchen and laundry circuit and the nameplate of each fixed appliance; count the first 10 kVA in full and the rest at 40 %; add the largest heating or cooling load and divide by 240 V.
Is 100 amp service enough for a house?
For a small house with gas heat and a few electric appliances it often is. The example 2,000 ft² house with a dryer, range, water heater and central air comes to 99 A.
When do I need 200 amp service?
When the calculated load is over 175 A, often with electric heat, a heat pump with backup heat, an EV charger or a large house.
Does this work outside the US?
The method is from the US National Electrical Code. Other countries have their own rules for house supplies.
Calculadoras relacionadas
Fuentes
- [1]Dwelling Load Calculations Per the National Electrical Code (M. Holt, EC&M, 2022-01-06), 2020 NEC. EC&M. NEC 220.82 optional method for a dwelling on one 120/240 V or 120/208 V service of 100 A or more: 3 VA per ft² (outside dimensions, no porches, garages or unfinished space), 1,500 VA per small-appliance and laundry circuit, fixed appliances at nameplate; first 10 kVA at 100 %, the rest at 40 %; plus the largest of air conditioning 100 %, heat pump 100 % (with supplementary heat 65 %), space heating 65 % for three units or less, 40 % for four or more; amperes = VA / voltage; disconnect per 240.6(A). Worked example: 89,398 VA / 240 V = 372 A, 400 A service.. Comprobado el 18 de noviembre de 2026
- [2]Load Calculation Form (Optional Format), NEC 220.82 (2019-07-02). City of Bellevue, Development Services. Permit worksheet layout: general loads summed, first 10 kVA at 100 %, remaining at 40 %; air conditioning 100 %, electric heating 100/65/40 %; largest heating or cooling; amps at 240 V.. Comprobado el 18 de noviembre de 2026