Solar battery and inverter calculator

Size a home battery for power cuts or an off-grid cabin: how many kWh and Ah to buy, what inverter carries your appliances and their starting surge, and how many panels refill it in the darkest month.

What the battery must carry

Enter how much electricity you need from the battery and for how long. You get the battery size, the inverter power and, for a cabin off the grid, the panels for the darkest month.

kWh/day

For backup, count only what must keep running. The electricity usage calculator adds it up.

h

How long a typical power cut lasts where you live.

Battery

%

The share of the nominal capacity you may use. The battery data sheet gives the depth of discharge.

%

From the inverter data sheet; good inverters reach about 95 %.

Battery voltage

kWh

Nominal kWh of the battery or module you plan to buy, to count how many.

Inverter

W

Everything that can run at the same time, in watts.

W

Peak plus the extra draw of the largest motor starting, about 3 × its power.

%

Inverters give less when warm. Example: 3,700 W instead of 4,000 W at 40 °C is 92.5 %.

Battery capacity to buy2.6 kWh
Add this calculator to your website

Free for any website: paste this code where the calculator should appear. It keeps itself up to date, fits its height to the content and links back to the full page with the explanations.

使い方

  1. 01Choose backup for power cuts, or off-grid for a cabin or a home without a grid connection.
  2. 02Enter how many kWh a day the loads use. For backup, count only what must keep running: fridge, lights, router, heating pump.
  3. 03Enter how many hours of backup you want, or how many days without sun an off-grid system must bridge.
  4. 04Choose the battery type and check the usable share and the inverter efficiency against the data sheets.
  5. 05Enter the peak load and starting surge (the electricity usage calculator gives both) to size the inverter.
  6. 06For off-grid, enter where the panels will be, their tilt and direction: the calculator finds the darkest month and the panels it needs.

計算方法

The battery must deliver the energy of your loads for the whole period through the inverter, and must not be emptied below its reserve. So the energy is divided by the inverter efficiency and by the usable share of the nominal capacity.

Energy for the loads
E = kWh per day × days (or hours ÷ 24)
Nominal capacity
C = E ÷ inverter efficiency ÷ usable share
Amp-hours
Ah = C (Wh) ÷ battery voltage
Inverter
continuous ≥ peak load ÷ output when hot; surge ≥ starting surge
Off-grid panels
kWp = kWh per day ÷ (sun hours per day in the darkest month × 0.67)

The PVGIS manual uses a cut-off of 40 % charge for lead-acid batteries and says lithium batteries can go down to 20 %, so the usable shares are 60 % and 80 %. Many lithium data sheets allow more; use the depth of discharge from yours.

Inverter data sheets give a continuous rating, a lower rating at higher temperature and a short peak rating. A Victron MultiPlus-II 48/5000, for example, gives 4,000 W at 25 °C, 3,700 W at 40 °C and 9,000 W peak.

Sun hours are the daily irradiation on the panels in kWh/m², taken from PVGIS for every month. The ratio 0.67 is the fixed performance ratio PVGIS uses for off-grid systems; it covers the losses of the panels, the charge controller and the battery.

計算例

Eight hours of backup for 6 kWh a day

  1. Energy for the loads: 6 × 8 ÷ 24 = 2 kWh.
  2. Lithium battery, 80 % usable, inverter 95 %: 2 ÷ 0.95 ÷ 0.8 = 2.63 kWh nominal.
  3. At 48 V: 2,630 Wh ÷ 48 V = 55 Ah.
  4. Off-grid instead, 3 kWh a day for 2 days: 6 ÷ 0.95 ÷ 0.8 = 7.9 kWh. If the darkest month gives 1.0 sun hour a day on the panels: 3 ÷ (1.0 × 0.67) = 4.5 kWp.

発注時のポイント

Back up only what matters

Heating pump, fridge, freezer, lights, router and a few sockets usually need a fraction of the daily use of the whole home. A smaller battery then lasts longer.

Check the starting current

Pumps, compressors and fridges draw several times their running power when they start. Compare the surge with the inverter's peak rating, or the motor-start rating some batteries give.

Tilt off-grid panels steeply

In winter the sun is low. A steeper tilt catches more of it and lets snow slide off; try a few angles and watch the panels needed for the darkest month.

Mind the cold

Batteries deliver less when cold and lithium batteries must not be charged below their minimum temperature. Keep them indoors or heated.

よくある間違い

  • Buying the nominal capacity you need as usable energy. The reserve and the inverter take their share.
  • Sizing the inverter for the average load. It must carry everything that can run at once, and the starting surge.
  • Sizing off-grid panels for the yearly average. In winter they make a fraction of their summer output.
  • Mixing up Ah at 12 V and at 48 V. The same Ah at 48 V store four times the energy.

よくある質問

How big a battery do I need?

Multiply the daily energy of the loads by the days or hours of backup, then divide by the inverter efficiency and the usable share. 2 kWh of loads need about 2.6 kWh of lithium battery.

How do I convert kWh to Ah?

Divide the watt-hours by the battery voltage. 5 kWh at 48 V is 5,000 ÷ 48 = 104 Ah; at 12 V it is 417 Ah.

What size inverter do I need?

Its continuous rating must exceed the peak load, with a margin if it stands somewhere warm, and its peak rating must exceed the starting surge.

How many panels does an off-grid home need?

Enough for the darkest month you want to cover. The calculator takes that month's sunshine from PVGIS for your place and tilt.

出典

  1. [1]PVGIS 5 user manual: off-grid PV systems. European Commission, Joint Research Centre. Battery cut-off: lead-acid batteries stop at 40 % charge, lithium-ion can go down to 20 %. Battery energy = voltage × capacity in Ah, using the nominal capacity. Off-grid systems are calculated with a fixed performance ratio of 0.67. Monthly in-plane irradiation for the darkest month comes from the same database.. 確認日: 2026年11月18日
  2. [2]MultiPlus-II 230 V technical specifications. Victron Energy. Inverter efficiency up to 95 % (48/3000). Ratings of the 48/5000: 5000 VA, 4000 W continuous at 25 °C, 3700 W at 40 °C, 9000 W peak; 48/3000: 2400 W at 25 °C, 2200 W at 40 °C, 5500 W peak.. 確認日: 2026年11月18日
  3. [3]Powerwall 3 data sheet. Tesla. Example of a home battery: 13.5 kWh usable, 11.04 kW continuous, motor starting rated as 185 A locked-rotor current, 89 % solar-to-battery-to-home efficiency.. 確認日: 2026年11月18日
  4. [4]Energy Series: Estimating Appliance and Home Electronic Energy Use (BSE-301NP, 2020). Virginia Cooperative Extension, Virginia Tech. A motor draws about three times its running current while starting.. 確認日: 2026年11月18日

計算式と出典の最終確認日: 2026年11月18日。 計算方法