Underfloor heating calculator
Work out how much heating pipe a room needs, how many circuits it takes and how long each one is, from the floor size, the pipe spacing and the distance to the manifold.
Room
Pipe in the room = area / spacing. Each circuit adds the lead to the manifold and back and stays within the maker's maximum length (150 m in the Uponor tables).
Heated floor
Kitchen units, built-in wardrobes, a shower tray: no pipe under them.
Circuits
One way, along the route the pipe takes.
From your pipe maker. The Uponor tables for 14 and 16 mm pipe use 150 m.
From the heat loss calculator, to see the output the floor has to give.
Add this calculator to your website
Free for any website: paste this code where the calculator should appear. It keeps itself up to date, fits its height to the content and links back to the full page with the explanations.
Nasıl kullanılır?
- 01Enter the room length and width, and the floor area that gets no pipe, such as under kitchen units or a shower tray.
- 02Pick the pipe spacing from your heating design. Closer spacing gives more heat and needs more pipe.
- 03Enter the distance from the manifold to the room and the longest circuit your pipe maker allows.
- 04Read the pipe to buy, the number of circuits and the length of each one. Add the room heat load to see the output the floor has to give.
Nasıl hesaplanır?
Pipe laid in parallel runs covers the floor at a fixed spacing, so the length in the room is the area divided by the spacing. Each circuit also runs to the manifold and back.
- Pipe in the room
- L = A / s
- Circuits
- n = ⌈L / (Lmax − 2 × d)⌉
- Total pipe
- L + n × 2 × d
- To buy
- total × 1.10
At 12 in spacing one foot of tube covers one square foot; at 9 in it takes 1.3 ft, at 6 in 2 ft and at 4 in 3 ft (Plumbing apprenticeship text, BCcampus). The same text adds the tails to the manifold and recommends ordering 10 % more tube.
A circuit may not be longer than the pump can push water through. The Uponor tables for 14 and 16 mm pipe are built on 150 m per circuit including 2 × 5 m of connection; for ½ in tube 300 ft is the usual limit at a 20 °F drop.
For ½ in tube the US text links spacing to the output the floor must give: 12 in up to 25 Btu/(h·ft²), 9 in up to 30 and 6 in up to 40. Above 40 occupied rooms need heat from another source.
Çözümlü örnek
A 5 × 4 m living room, 15 cm spacing, manifold 5 m away
- Pipe in the room: 20 m² / 0.15 m = 133 m.
- One circuit: 133 m + 2 × 5 m = 143 m, under the 150 m limit.
- To buy: 143 m + 10 % = 158 m.
- At 10 cm the room needs 200 m of pipe in the floor, which takes two circuits.
Sipariş için ipuçları
Keep circuits about equal
Circuits of similar length need similar flow and are easier to balance at the manifold. Split a big room into equal parts rather than one long and one short circuit.
Mind the coil length
Pipe is sold in coils. Plan each circuit from one piece of pipe, without joints in the screed.
Plan the floor build-up first
The pipe sits in or under the screed. Check the build-up height with the screed calculator before you order.
Sık yapılan hatalar
- Leaving out the leads. A manifold in the hallway can add 10 to 20 m of pipe per circuit.
- Counting the area under kitchen units. No pipe goes there, and it would only heat the cupboards.
- Making one circuit too long. A circuit over the maker’s limit gets too little flow and stays cold at the end.
- Choosing a wide spacing for a room with a high heat loss. The floor then cannot give enough heat at a comfortable surface temperature.
Sorular
How much underfloor heating pipe per m²?
Divide one by the spacing: 10 m/m² at 10 cm, 6.7 m/m² at 15 cm, 5 m/m² at 20 cm. Add the leads to the manifold and about 10 % for bends and cuts.
How long can one underfloor heating circuit be?
As long as the pipe maker allows. The Uponor tables for 14 and 16 mm pipe use 150 m including the leads; for ½ in tube about 300 ft is the usual limit.
How much tubing per square foot for radiant floor heat?
1 ft per ft² at 12 in spacing, 1.3 ft at 9 in, 2 ft at 6 in and 3 ft at 4 in, plus the tails to the manifold.
What pipe spacing should I use?
It follows from the heat the floor must give. For ½ in tube: 12 in up to 25 Btu/(h·ft²), 9 in up to 30 and 6 in up to 40. A heating engineer sets it for each room.
İlgili hesaplayıcılar
Kaynaklar
- [1]Uponor Klett Twinboard, Technische Information (1120374 v1, 01/2021). Uponor. Pipes 14 × 2.0 and 16 × 2.0 mm, spacings 10 to 30 cm; design tables based on a maximum heating circuit length of 150 m and 250 mbar per circuit including 2 × 5 m connection line.. Kontrol tarihi: 11 Kasım 2026
- [2]Plumbing Apprenticeship Level 3, Learning Task 2: Select and Size Piping. BCcampus OpenText (Industry Training Authority BC). 300 ft is the maximum length of a ½ in loop at a 20 °F temperature drop. Tubing per square foot: 1 ft at 12 in spacing, 1.3 ft at 9 in, 2 ft at 6 in, 3 ft at 4 in; tails from the manifold to the room and back are added; order 10 % more tube. ½ in tube spacing by floor output: 12 in up to 25 Btu/h·ft², 9 in for 25–30, 6 in for 30–40; above 40 Btu/h·ft² occupied areas need supplemental heat.. Kontrol tarihi: 11 Kasım 2026
Formüllerin ve kaynakların son kontrol tarihi: 11 Kasım 2026. Nasıl hesaplıyoruz?