Attic ventilation
Enter the attic floor size: see the net free vent area the IRC asks for, how to split it between ridge and soffit vents, and how much ridge vent and how many intake vents to buy.
Attic
The attic floor, the ceiling below it: usually the house footprint without the overhangs.
Vent layout
40–50 % of the vent area high on the roof, no more than 3 ft (0.9 m) below the ridge, the rest at the soffits: 1 per 300.
Vents
From the vent’s label; Air Vent’s ShingleVent II 12-inch is 18 sq in per foot (381 cm²/m).
The net free area printed on the vent or its sheet, not its outside size.
Додайте цей калькулятор на свій сайт
Калькулятор безкоштовний для будь-якого сайту. Вставте код туди, де має з'явитися калькулятор. Калькулятор оновлюється автоматично, підлаштовує висоту під вміст і містить посилання на повну сторінку з поясненнями.
Як користуватися
- 01Enter the length and width of the attic floor, the ceiling of the rooms below.
- 02Pick the vent layout: ridge vents with soffit vents (balanced), or any other layout, such as gable vents only or a ridge vent with no soffit vents.
- 03Enter the net free area of the ridge vent from its label, and of one soffit vent if you want a vent count. The result shows the vent area, the ridge vent length and the number of soffit vents.
Як виконується розрахунок
A 30 × 42 ft attic with a ridge vent and soffit vents needs 605 sq in of net free vent area: about 303 sq in at the ridge and the rest at the soffits. With 18 sq in per foot of ridge vent, that is about 17 ft of ridge vent.
- Balanced vents
- net free area = attic floor area ÷ 300
- Other layouts
- net free area = attic floor area ÷ 150
- Split
- high vents 40–50 % (the calculator shows 50 %), soffit vents the rest
- Ridge vent length
- high-vent area ÷ net free area per foot of vent
The rules are the International Residential Code ones, as the U.S. Department of Energy’s Building America Solution Center explains them. The total net free area must be at least 1/300 of the attic area when 40 to 50 % of it is high on the roof, no more than 3 ft (0.9 m) below the highest point and at least 3 ft (0.9 m) above the eave vents, with the rest in soffit or eave vents. Without that balance, for example when there are no soffit, eave or low gable vents, it must be 1/150.
Net free area is the open area of a vent after screens and louvers take their share, so it is smaller than the vent’s outside size. Manufacturers print it on the vent or its data sheet. Air Vent rates its 12-inch ShingleVent II ridge vent at 18 sq in per linear foot and its 9-inch version at 6 sq in: the rating follows the height of the ribs under the vent, not the width.
The calculator works in square inches (square centimetres in metric) and rounds up. Local codes can amend the IRC, so check with your building department.
Приклад розрахунку
A 30 × 42 ft (9.1 × 12.8 m) attic with ridge and soffit vents
- Attic floor: 30 × 42 = 1,260 sq ft.
- Net free area: 1,260 ÷ 300 = 4.2 sq ft = 605 sq in (rounded up).
- High vents: half, 303 sq in; at least 40 %, 242 sq in. Soffit vents: the other 303 sq in.
- Ridge vent at 18 sq in per foot: 303 ÷ 18 = 16.8 ft, so 17 ft.
- Without balanced vents: 1,260 ÷ 150 = 1,210 sq in.
- Metric: the same attic is 9.1 × 12.8 m = 117 m²; 117 ÷ 300 = 0.39 m², about 3,900 cm².
Як правильно замовити
Use the label figure
Enter the net free area printed on the vent or its sheet. A screened vent has much less open area than its outside size: BASC takes 60 % for most screened vents, so a vent that must supply 303 sq in net needs about 505 sq in of outside area.
Keep the soffits open
BASC asks for at least 1 in (25 mm) of space between insulation and roof sheathing at the eaves, and a soffit vent in each rafter bay.
Keep the split near half
In the balanced layout 40–50 % of the area goes high on the roof and the rest at the soffits.
Поширені помилки
- Using the outside size of a vent as its net free area: at BASC’s 60 % for screened vents, an 8 × 16 in vent gives about 77 sq in, not 128.
- Counting a ridge vent with no soffit intake as balanced: without low vents the 1/150 rule applies.
- Measuring the roof surface instead of the attic floor: the ratio is to the area of the space being vented.
Запитання
How much attic ventilation do I need?
1 sq ft of net free area per 300 sq ft of attic floor with balanced ridge and soffit vents, and 1 per 150 otherwise. A 1,260 sq ft attic needs 605 sq in or 1,210 sq in.
How many soffit vents do I need?
Divide the soffit share, half of the total in a balanced layout, by the net free area of one vent. For 303 sq in and vents rated at 50 sq in (323 cm²) each, that is 7 vents.
How much ridge vent do I need?
The high share divided by the vent’s net free area per foot: 303 sq in at 18 sq in per foot is about 17 ft.
What is the 1/300 rule?
The IRC lets the vent area be 1/300 of the attic area instead of 1/150 when 40 to 50 % of it is high on the roof and the rest at the eaves.
Пов'язані калькулятори
Джерела
- [1]Calculating Attic Passive Ventilation. U.S. Department of Energy, Building America Solution Center (PNNL). IRC attic ventilation: net free area not less than 1/300 of the attic area when 40–50 % of it is high on the roof (no more than 3 ft below the highest point, at least 3 ft above the eave vents) and the rest in soffit or eave vents; 1/150 without that balance; example 30 × 42 ft = 1,260 sq ft → 1/300 = 605 sq in, half high = 303 sq in; 1/150 = 1,210 sq in; keep 1 in between insulation and sheathing. Перевірено 24 листопада 2026 р.