Garage heater size
Work out how big a heater your garage needs: the heat it loses through the walls, roof, door, windows, air and slab on the coldest day, in Btu/h and kW.
Garage
The wall with the garage door, measured inside.
Attached to the house
The temperature you want while you work in the garage.
The coldest design temperature for your town, from your national heating standard or your heating engineer.
Walls, roof and openings
U 1.31 W/(m²·K)
U 2.73 W/(m²·K)
Width × height of the door opening. A 16 × 7 ft door is 112 sq ft.
U 6.81 W/(m²·K)
Add a walk-in door here too if it is mostly glass.
Glass
Air leaks, floor and wind
Modine uses one or two. Take 2 for a drafty door or one you open often.
Modine gives 50 Btu/h per foot of exposed slab edge without insulation. Enter 0 to leave the floor out.
Exposed to prevailing winds
Додайте цей калькулятор на свій сайт
Калькулятор безкоштовний для будь-якого сайту. Вставте код туди, де має з'явитися калькулятор. Калькулятор оновлюється автоматично, підлаштовує висоту під вміст і містить посилання на повну сторінку з поясненнями.
Як користуватися
- 01Enter the inside width, depth and wall height of the garage, and say whether one side wall is shared with the heated house.
- 02Enter the temperature you want to keep and your design outdoor temperature, the cold your heating has to cover.
- 03Pick the walls, the roof or ceiling and the garage door, and enter the door and window areas. For an insulated door, enter the U-factor the manufacturer gives for the whole door.
- 04Under "Air leaks, floor and wind", change the air changes, the slab edge figure or the 10 % wind allowance if you need to, and read the heater output.
Як виконується розрахунок
A 24 × 24 ft (7.3 × 7.3 m) garage held at 50 °F (10 °C) when it is −5 °F (−20.6 °C) outside needs about 42,100 Btu/h (12.3 kW) uninsulated, or 25,700 Btu/h (7.5 kW) with insulated walls and roof. A heater has to replace the heat the garage loses on a design day. The calculator follows the heat loss worksheet Modine publishes for its unit heaters: each surface loses area × U × temperature difference, leaking air carries heat out, and the slab loses heat at its edge.
- Walls, roof, door, windows
- area × U × (inside − outside)
- Air
- volume × air changes per hour × (inside − outside) ÷ 55, in Btu/h with ft³ and °F (0.34 Wh/(m³·K) in metric)
- Slab
- exposed perimeter × 50 Btu/h per ft (48 W/m)
- Total
- sum × 1.10 when the garage stands in prevailing winds
The U-factors come from Modine form 75-202, in Btu/h per sq ft per °F, with W/(m²·K) in brackets: an uninsulated 2 × 4 frame wall 0.23 (1.31) and 0.07 (0.40) with 3 in of insulation, a 1 in wood roof deck 0.48 (2.73) and 0.17 (0.97) with a 1 in blanket, corrugated metal 1.50 (8.52) bare and 0.08 (0.45) with a 3 in blanket, a single-sheet metal door 1.20 (6.81), single glass 1.13 (6.42) and double glass 0.69 (3.92). The calculator shows each preset with its U so you can see what it uses.
Modine says infiltration is usually one or two air changes per hour; the calculator starts at one. For the slab it multiplies the exposed edge by an F factor of 50 Btu/h per foot for an uninsulated edge, the same at every design temperature in its table, from −19 to 15 °F. A wall shared with the heated house is left out, on the assumption that the house is at least as warm as the garage.
Garage door manufacturers print an R-value for the door section. DASMA, the door manufacturers’ association, notes that this is not the R-value of the installed door: codes use the U-factor of the whole door, tested to ANSI/DASMA 105. Use that figure for an insulated door.
The result is the output the heater must deliver. Modine sizes a heater by matching the total to the heater’s output, and adds 10 % for areas exposed to prevailing winds.
Приклад розрахунку
A 24 × 24 ft two-car garage, before and after insulation, and a 6 × 6 m garage
- 24 × 24 ft, 9 ft walls, detached, 16 × 7 ft steel door, 50 °F inside, −5 °F outside (Chicago’s 99.6 % design temperature), ΔT 55 °F (7.3 × 7.3 m, 2.7 m walls, 10 °C inside, −20.6 °C outside, ΔT 30.6 K).
- Uninsulated frame walls: (96 × 9 − 112) × 0.23 × 55 = 9,513 Btu/h. Wood roof: 576 × 0.48 × 55 = 15,206. Door: 112 × 1.20 × 55 = 7,392. Air, one change per hour: 5,184 ft³ × 55 ÷ 55 = 5,184 by Modine (5,204 with 0.34 Wh/(m³·K)). Slab: 96 ft × 50 = 4,800. Total about 42,100 Btu/h (12.3 kW), 73 Btu/h per sq ft.
- With 3 in of wall insulation (0.07) and a 1 in blanket under the roof (0.17): walls 2,895, roof 5,386, the rest the same, about 25,700 Btu/h (7.5 kW). The steel door is now 29 % of the load. As an electric heater at 240 V that is about 7,500 W ÷ 240 = 31 A.
- Metric: 6 × 6 m, 2.5 m walls, uninsulated frame and roof, 10 m² steel door, 10 °C inside and −15 °C outside: walls 1,633 W, roof 2,453, door 1,703, air 765, slab 24 m × 48.1 W/m = 1,154, total 7.7 kW (26,300 Btu/h). Insulated walls and roof bring it to 5.0 kW.
Як правильно замовити
Insulate the roof first, then the door
In the uninsulated example the roof loses the most heat, 15,206 of 42,100 Btu/h. Once the walls and roof are insulated, the single-sheet steel door is the largest part. Change one preset at a time in the calculator and watch the bars to see where an upgrade pays.
Use a real design temperature
The design temperature is the cold your heater has to keep up with, not the coldest night on record. ASHRAE’s 99.6 % figure is the usual one in the US: Chicago −5.0 °F (−20.6 °C), Atlanta 18.8 °F (−7.3 °C) in the 2005 tables. Your HVAC contractor or code office can give the local value.
Fuel-burning heaters
The U.S. Consumer Product Safety Commission warns that a fuel-burning heater that is improperly installed or poorly maintained can produce carbon monoxide, and that an oversized heater can use up the available oxygen. Follow the manufacturer’s combustion-air instructions and have gas heaters inspected every year.
Поширені помилки
- Sizing by square feet alone: the same 24 × 24 ft garage needs about 42,100 Btu/h uninsulated and 25,700 insulated at −5 °F, and 26,000 uninsulated at Atlanta’s 18.8 °F.
- Entering the section R-value of an insulated door as if it were the door’s R. Use the whole-door U-factor.
- Comparing the result with a gas heater’s input rating. The load is matched to the output.
- Forgetting the air: a drafty door at two air changes adds another 5,200 Btu/h in the insulated example.
Запитання
How many BTU to heat a 2 car garage?
It depends on the insulation and your climate. A 24 × 24 ft garage with 9 ft walls, held at 50 °F when it is −5 °F outside, needs about 42,100 Btu/h uninsulated and 25,700 Btu/h with insulated walls and roof, by the Modine method.
How many BTU per square foot for a garage?
In the examples above, 73 Btu/h per sq ft uninsulated and 45 insulated at a 55 °F difference. The figure moves with the temperature difference and the door, so work it out from your own garage instead of using a fixed number.
Is 30,000 BTU enough for a 2 car garage?
For the insulated 24 × 24 ft example at −5 °F, yes: it needs about 25,700 Btu/h, or 28,200 with the 10 % wind allowance. Uninsulated it needs about 42,100, so 30,000 would not hold 50 °F on the design day.
How many Btu/h is 1 watt?
One watt is 3.412 Btu/h, so 1 kW is about 3,412 Btu/h and 5 kW about 17,100 Btu/h.
Пов'язані калькулятори
Джерела
- [1]Heat Loss Calculation, form 75-202.7 (September 2015). Modine Manufacturing Company (via Global Industrial). Btu/h = net sq ft × temperature difference × U for walls, windows, doors and roof; infiltration Btu/h = ft³ × ΔT × air changes per hour ÷ 55, usually one or two air changes; floor = exposed perimeter × F factor, F = 50.00 for an uninsulated slab edge at every listed design temperature from −19 to 15 °F; add 10 % for areas exposed to prevailing winds; pick a heater whose output covers the total. U (Btu/(h·ft²·°F)): frame wall 0.23 uninsulated, 0.07 with 3 in insulation; metal wall 1.17, 0.22 with 1 in blanket, 0.08 with 3 in; 8 in concrete block 0.39 (cinder) and 0.52 (gravel); 8 in poured concrete 0.25; corrugated metal roof 1.50, 0.23 with 1 in, 0.08 with 3 in; 1 in wood roof 0.48, 0.17 with 1 in blanket; single glass 1.13, double glass 0.69; metal door, single sheet 1.20; wood door 1 in 0.64, 2 in 0.43. Перевірено 21 листопада 2026 р.
- [2]Garage door thermal performance: section R-value vs. door U-factor (TDS 163). DASMA. The R-value printed for a door section is not the R of the installed door; codes use the U-factor of the whole door tested to ANSI/DASMA 105, and R and U of a door are not reciprocals. Перевірено 21 листопада 2026 р.
- [3]ASHRAE Temperatures for Major US Cities (2005 ASHRAE Handbook of Fundamentals). FGIA. 99.6 % heating dry-bulb design temperatures, for example Minneapolis −14.9 °F, Chicago −5.0 °F, Boston 7.7 °F and Atlanta 18.8 °F. Перевірено 21 листопада 2026 р.
- [4]CPSC Warns of Hazards from Heaters and Fireplaces (news release, 2004-12-10). U.S. Consumer Product Safety Commission. Improperly installed or poorly maintained fuel-burning heaters can produce carbon monoxide; an oversized heater can deplete the available oxygen; follow the manufacturer’s combustion-air instructions; have gas heaters inspected every year. Перевірено 21 листопада 2026 р.
- [5]Heizlast-Berechnung nach DIN EN 12831, Teil 1 (E. Held, SBZ Monteur 01/2005). SBZ Monteur. ΦT = A × U × (θi − θe); ΦV = V̇ × 0.34 Wh/(m³K) × (θi − θe). Minimum air change 0.5 1/h for living rooms, 1.5 for a bathroom with window, 1.0 for an office; standard room temperatures 20 °C living, 24 °C bathroom, 15 °C heated corridors. Design outdoor temperature from the National Annex by place. Перевірено 11 листопада 2026 р.
- [6]The Physics of Heat and Air Flow (A. Bailes III, 2018-05-02). ACCA HVAC Blog. Sensible heat of air: Btu/h = 1.08 × cfm × ΔT (0.075 lb/ft³ × 0.24 Btu/(lb·°F) × 60 min/h), near sea level and room temperature. Перевірено 11 листопада 2026 р.
Формули та джерела востаннє перевірено 21 листопада 2026 р.. Як ми рахуємо