Heat pump size
Check whether a heat pump covers your house on the coldest day: capacity at your design temperature against the heat load, the balance point, and the backup heat needed.
House and climate
The heat loss of the house at the design temperature, from a Manual J or EN 12831 calculation or the heat loss calculator.
MCS uses 21 °C for heat pump sizing in the UK.
The coldest temperature the heating is designed for, from your contractor or local data.
Heat pump
Two maximum heating capacities from the model's data sheet or extended performance table, for example at 47 °F and 5 °F, or at 7 °C and −15 °C. Take the point closest to your design temperature as one of them.
Додайте цей калькулятор на свій сайт
Калькулятор безкоштовний для будь-якого сайту. Вставте код туди, де має з'явитися калькулятор. Калькулятор оновлюється автоматично, підлаштовує висоту під вміст і містить посилання на повну сторінку з поясненнями.
Як користуватися
- 01Enter the design heat load of the house and the design outdoor temperature it applies to. The heat loss calculator gives a room-by-room figure.
- 02Enter the indoor temperature you heat to.
- 03From the heat pump’s data sheet, enter two maximum heating capacities and the outdoor temperatures they are rated at, one of them at or below your design temperature if the sheet has it.
- 04Read the share of the load the heat pump covers on the design day, the backup heat it would need, and the balance point.
Як виконується розрахунок
Choose a heat pump whose capacity at your design temperature is 100 to 115 % of the house’s heat load, or 75 to 85 % if you add backup heat (NEEP). Size it to that heat load, not to floor area. A house that loses 30,000 Btu/h (8.8 kW) at 5 °F, with a heat pump that gives 25,200 Btu/h at 5 °F, is 84 % covered: 4,800 Btu/h (1.4 kW) has to come from backup heat on the design day, and the heat pump keeps up alone above about 11.7 °F (−11.3 °C); below that, backup heat runs.
- House load at t
- design load × (indoor − t) ÷ (indoor − design temperature)
- Capacity at t
- straight line through the two data-sheet points
- Coverage
- capacity at design temperature ÷ design load
- Backup heat
- design load − capacity, when positive
- Balance point
- outdoor temperature where the two lines cross
The load line comes from how heat loss works: through walls, windows and air it is proportional to the difference between inside and outside (DIN EN 12831, via SBZ), so it falls to zero at the indoor temperature. The capacity line is drawn straight between the two points you enter. That is the calculator’s simplification; real capacity curves bend, so use the data-sheet point nearest your design temperature.
The judgement follows NEEP’s guide to sizing heat pumps in cold climates (hosted by the U.S. Department of Energy). To heat a house on its own, the heat pump should give 100 to 115 % of the heating load at the design temperature, without auxiliary heat. The alternative is 75 to 85 % of the load with just enough supplemental heat. NEEP also advises against multi-zone outdoor units above 120 % of the design load.
The Building America Solution Center (PNNL) describes the same choice: size to the full design load, where a slight oversize for heating is acceptable, or to a share such as 80 % and use auxiliary heat in the coldest part of the winter. It defines the balance point as the lowest outdoor temperature at which the unit provides all the heating the home needs.
Приклад розрахунку
A 30,000 Btu/h house at 5 °F and a 9 kW house at −15 °C
- Design load 30,000 Btu/h (8.8 kW) at 5 °F (−15 °C), indoor 70 °F (21 °C). The data sheet gives 36,000 Btu/h at 47 °F and 25,200 Btu/h at 5 °F, the 70 % ratio the ENERGY STAR Cold Climate criteria ask for at minimum.
- Coverage: 25,200 ÷ 30,000 = 84 %, inside NEEP’s 75 to 85 % band for a system with backup. Backup at 5 °F: 4,800 Btu/h (1.4 kW). Balance point 11.7 °F (−11.3 °C). Nominal size 36,000 ÷ 12,000 = 3 tons.
- A model with 30,000 Btu/h at 5 °F would cover 100 %, with no backup and a balance point at the design temperature.
- Metric: 9 kW at −15 °C, indoor 21 °C (the design inside temperature in the UK’s MCS 031, which sets the indicative capacity equal to the heat loss); the heat pump gives 10 kW at 7 °C and 7 kW at −15 °C. Coverage 7 ÷ 9 = 78 %, backup 2 kW, balance point −9.8 °C.
Як правильно замовити
Read the cold-weather capacity
A heat pump’s headline rating is at mild temperatures, such as 47 °F or 7 °C. What matters for sizing is its maximum capacity at your design temperature, from the extended performance table. The ENERGY STAR Cold Climate criteria ask for at least 70 % of the 47 °F capacity at 5 °F, so a certified 36,000 Btu/h unit gives at least 25,200 at 5 °F; a unit without that rating may give less.
Start from a heat loss calculation
The load you enter decides the answer. Use a Manual J or EN 12831 calculation, or add up the rooms in the heat loss calculator, rather than a figure per square foot.
Keep backup heat for backup
NEEP advises that supplemental heat should be shut off unless it is needed. Set the controls so the backup only runs below the balance point.
Поширені помилки
- Sizing from the 47 °F rating: in the example that gives 120 % on paper and 84 % on the design day.
- Using a floor-area rule instead of the design heat load.
- Oversizing far past the load: NEEP gives 100 to 115 % for a heat pump that heats on its own.
- Leaving the backup heat out of the electrical plan when the heat pump covers less than the full load: add it in the electrical load calculator.
Запитання
What size heat pump do I need?
One whose heating capacity at your design outdoor temperature is 100 to 115 % of the house’s design heat load to heat on its own, or 75 to 85 % with backup heat, by NEEP’s guidance. Get the load from a heat loss calculation and the capacity from the model’s extended data.
Is it better to undersize or oversize a heat pump?
NEEP’s ranges allow a little oversize (up to 115 %) for a heat pump that heats alone, and a planned undersize (75 to 85 %) when backup heat covers the coldest hours.
What is the balance point of a heat pump?
The lowest outdoor temperature at which the heat pump alone provides all the heat the home needs (PNNL). Below it, backup heat makes up the difference.
How many tons is a 36,000 BTU heat pump?
Three tons: one ton is 12,000 Btu/h.
Пов'язані калькулятори
Джерела
- [1]Cold Climate Heat Pump Sizing and Selection. PNNL, Building America Solution Center. Approach 4: size to meet the design heating load at the design heating temperature, a safety factor to slightly oversize is acceptable; approaches 1–3 need auxiliary heat in the colder part of winter, approach 3 sizes to a share of the design load (for example 80 %); balance point = the lowest outdoor temperature at which the unit provides all the heating. Перевірено 21 листопада 2026 р.
- [2]Guide to Sizing & Selecting Air-Source Heat Pumps in Cold Climates. NEEP (hosted by U.S. DOE). Full replacement: capacity at design temperature 100–115 % of the heating load without auxiliary heat; or design for 75–85 % of the load with just enough supplemental heat; avoid multi-zone units above 120 % of the design load; supplemental heat shut off unless needed. Перевірено 21 листопада 2026 р.
- [3]ASHP Specification Summary Table V4. NEEP. ENERGY STAR Cold Climate v6.1: capacity at 5 °F at least 70 % of the capacity at 47 °F; COP at 5 °F at least 1.75. Перевірено 21 листопада 2026 р.
- [4]MCS 031 Heat Pump Pre Sale Information and Calculations, Issue 4.0 (18/12/2024). MCS. Heat pump capacity (kW) = total heat loss Pt ÷ 1000, indicative only; design inside temperature 21 °C, design outside temperature from the postcode table. Перевірено 21 листопада 2026 р.
- [5]Heizlast-Berechnung nach DIN EN 12831, Teil 1 (E. Held, SBZ Monteur 01/2005). SBZ Monteur. ΦT = A × U × (θi − θe); ΦV = V̇ × 0.34 Wh/(m³K) × (θi − θe). Minimum air change 0.5 1/h for living rooms, 1.5 for a bathroom with window, 1.0 for an office; standard room temperatures 20 °C living, 24 °C bathroom, 15 °C heated corridors. Design outdoor temperature from the National Annex by place. Перевірено 11 листопада 2026 р.