Đến nội dung chính
Yardox
Phiên bản ngôn ngữ này đang được người bản ngữ biên tập. Một số cách diễn đạt có thể thay đổi.

Wire size for long runs: current rating and voltage drop

A cable has to pass two checks. It must carry the current without overheating, and it must not lose too much voltage on the way. On short runs the first check decides; on long runs, to a garden shed or a car charger, the second one usually does.

Cập nhật 18 tháng 11, 2026

Trả lời ngắn gọn

Pick the smallest size whose rated current covers the load, then check the drop: ΔU = 2 × length × current × resistance per length for single phase. Keep it within 3 % on a branch circuit. If it is over, go up a size.

Tính ngay

Tính tiết diện dây dẫn

Tiết diện dây đồng theo dòng điện, chiều dài và độ sụt áp.

Tính tiết diện dây dẫn →

Check 1: current

In the United States, NEC Table 310.16 gives the ampacity of copper conductors. For the small sizes, NEC 240.4(D) also caps the breaker: 15 A on 14 AWG, 20 A on 12 AWG, 30 A on 10 AWG. A load that runs for three hours or more counts as continuous, and the wire must carry 125 % of it (NEC 210.19(A)(1)).

In Germany and much of Europe, DIN VDE 0298-4 gives the current-carrying capacity Iz by installation method: in insulation, in conduit, on the wall, in free air. The breaker In must sit between the load current and Iz: Ib ≤ In ≤ Iz.

Small copper sizes in the US (NEC Table 310.16 via Cerrowire, NEC 240.4(D))
SizeAmpacity 60 °CAmpacity 75 °CBreaker limit
14 AWG15 A20 A15 A
12 AWG20 A25 A20 A
10 AWG30 A35 A30 A

Metric copper with PVC insulation, on a wall (method C), two loaded conductors, 30 °C (ABB Table 2): 1.5 mm² 19.5 A, 2.5 mm² 27 A, 4 mm² 36 A. In thermal insulation or in conduit the values are lower.

Check 2: voltage drop

Current flows out on one conductor and back on the other, so a single-phase run of length L has 2 × L of wire. The drop is that length times the current times the resistance per length. For three phase use √3 instead of 2.

PanelLoadIOne-way length LΔU = 2 × L × I × R
The current travels the length twice, out and back. The drop grows with length and current and falls with thicker wire.
  • NEC informational note: not more than 3 % on the branch circuit and 5 % for feeder and branch together.
  • Germany (DIN 18015-1, as given by ABB): 3 % behind the meter.
  • Resistance rises with temperature. The calculator uses 75 °C values from NEC Chapter 9 Table 8 for AWG and 70 °C, the limit of PVC insulation, for metric sizes.

Worked example: 120 V, 16 A, 100 ft

A 20 A circuit to a workshop, 100 ft one way, carrying 16 A.

  • 12 AWG carries 20 A, so it passes the current check.
  • Drop on 12 AWG (1.93 Ω per 1,000 ft): 2 × 100 × 16 × 1.93 / 1,000 = 6.2 V, 5.1 % of 120 V. Too much.
  • 10 AWG (1.21 Ω): 3.9 V, 3.2 %. Still over 3 %.
  • 8 AWG (0.778 Ω): 2.5 V, 2.1 %. This is the size the drop asks for.

Worked example: 230 V, 16 A, 25 m

A socket circuit to a garden building, 25 m one way, 16 A.

  • Resistance at 70 °C: R20 × (1 + 0.00393 × 50), about 1.2 times the 20 °C value.
  • 1.5 mm² (12.1 Ω/km at 20 °C): 2 × 25 × 16 × 14.5 / 1,000 = 11.6 V, 5.0 %.
  • 2.5 mm² (7.41 Ω/km): 7.1 V, 3.1 %. Just over 3 %.
  • 4 mm² (4.61 Ω/km): 4.4 V, 1.9 %. Passes.

As a check of the method, ABB's table gives 34 m as the longest three-phase run of 1.5 mm² at 16 A and 400 V for a 3 % drop. With the conductor at 30 °C the formula gives the same 34 m.

Sizing a cable is the first step. The connection itself, the protection and the test belong to a qualified electrician.

Câu hỏi thường gặp

What size wire for 20 amps at 100 feet?

For a 16 A load at 120 V, 8 AWG keeps the drop near 2 %. 12 AWG carries the current but drops about 5 %.

What voltage drop is acceptable?

The NEC recommends not more than 3 % on a branch circuit and 5 % in total. In Germany 3 % is the usual limit behind the meter.

Why does a longer cable need a thicker wire?

Resistance grows with length. Thicker copper has less resistance per metre, which keeps the drop down.

Is 2.5 mm² enough for 16 A?

For the current, yes, in most installation methods. For a long run, check the drop: at 16 A and 230 V, 2.5 mm² reaches 3 % at about 24 m.

Tính ngay

Tính tiết diện dây dẫn

Tiết diện dây đồng theo dòng điện, chiều dài và độ sụt áp.

Tính tiết diện dây dẫn →

Nguồn tham khảo

  1. [1]Kabel- und Leitungsdimensionierung (2CDC400027D0104 Rev. E, 2023-10), after DIN VDE 0298-4 and DIN VDE 0100-430. ABB Stotz-Kontakt. Table 2: current-carrying capacity Iz of copper PVC cables at 30 °C ambient for installation methods A1, A2, B1, B2, C and E, two or three loaded conductors, 1.5 to 50 mm². Rule Ib ≤ In ≤ Iz. 3 % voltage drop behind the meter (DIN 18015-1); Table 11 (1.5 mm², 16 A, 400 V: 34 m at 3 %) as a check of the drop formula.. Đã kiểm tra 10 tháng 11, 2026
  2. [2]Conductor resistance (IEC 60228 / DIN EN 60228, class 1 and 2). Bayka. Maximum DC resistance of plain copper conductors at 20 °C: 12.1 Ω/km for 1.5 mm² down to 0.387 Ω/km for 50 mm².. Đã kiểm tra 10 tháng 11, 2026
  3. [3]Conductor resistance (temperature correction after IEC 60228 Annex B). Electrical Cable Engineering. R(t) = R20 × (1 + 0.00393 × (t − 20)) for annealed copper.. Đã kiểm tra 10 tháng 11, 2026
  4. [4]Ampacity chart (NEC Table 310.16, copper, not more than three current-carrying conductors, 30 °C ambient). Cerrowire. Allowable ampacity of copper conductors 14 AWG to 1/0 AWG in the 60 °C and 75 °C columns.. Đã kiểm tra 10 tháng 11, 2026
  5. [5]NEC Chapter 9, Table 8: Conductor Properties. NFPA (copy hosted by NECA-IBEW Electricians). DC resistance of uncoated copper at 75 °C in Ω per 1,000 ft: 14 AWG 3.07 (solid) to 1/0 AWG 0.122.. Đã kiểm tra 10 tháng 11, 2026
  6. [6]National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (L. Mari, 2022-06-07). EEPower. NEC 240.4(D): overcurrent protection of copper conductors not more than 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG. 210.19(A)(1): conductors carry the noncontinuous load plus 125 % of the continuous load. 110.14(C): 60 °C column for equipment rated 100 A or less unless marked for 75 °C.. Đã kiểm tra 10 tháng 11, 2026
  7. [7]Voltage Drop Limitations on Branch Circuits (M. Holt, 2015-05-05). EC&M. NEC 210.19(A) Informational Note No. 4: not more than 3 % on the branch circuit and 5 % for feeder and branch circuit together.. Đã kiểm tra 10 tháng 11, 2026