Kurz gesagt
At a rainfall intensity of 1 in per hour, each square inch of downspout drains 1,200 sq ft of roof. Divide by your local design rainfall, multiply the roof plan area by a pitch factor, and use one downspout for every 50 ft of gutter at most.
Selbst rechnen
Dachrinnen-Rechner
Wie viele Fallrohre, welche Rinnengröße und wie viel Rohr für eine Dachseite nötig sind.
Dachrinnen-Rechner →The area that drains into a gutter
Measure the roof from above: the gutter length times the horizontal depth from the eave to the ridge. Steep roofs catch more wind-driven rain, so the Copper Development Association multiplies the plan area by a factor.
| Roof pitch | Factor |
|---|---|
| Flat to 3 in 12 | 1.00 |
| 4 to 5 in 12 | 1.05 |
| 6 to 8 in 12 | 1.10 |
| 9 to 11 in 12 | 1.20 |
| 12 in 12 | 1.30 |
Downspout size and count
CDA Table 10A lists, for many US cities, how many square feet of roof one square inch of downspout drains in the 5-minute storm that comes once in 10 years and once in 100 years. Chicago, for example: 180 sq ft for the 10-year storm, 130 for the 100-year storm.
- Downspout section needed = plan area × pitch factor / local sq ft per sq in.
- Use the actual inside section of the downspout, not its nominal size: a 2 × 3 in rectangular downspout has 4.80 sq in, a 3 × 4 in 10.31, a 3 in round 5.94, a 4 in round 11.04 (GutterSupply).
- At least one downspout per 50 ft of gutter.
- CDA asks for downspouts of at least 7 sq in, except on small areas such as porches. A 2 × 3 in downspout is below that.
Worked example: Chicago, 40 ft gutter
The gutter is 40 ft long, the depth to the ridge is 15 ft, the pitch is 6 in 12.
- Plan area: 40 × 15 = 600 sq ft. With the factor 1.10: 660 sq ft.
- 10-year storm, 180 sq ft per sq in: 660 / 180 = 3.7 sq in of downspout.
- One 3 × 4 in downspout (10.31 sq in) drains 10.31 × 180 = 1,856 sq ft. One is enough, and 40 ft is within the 50 ft limit.
- Designing for the 100-year storm (130 sq ft per sq in): 660 / 130 = 5.1 sq in, still one 3 × 4 in downspout.
Metric roofs: gutter and pipe sizes
European gutter makers publish tables by roof plan area for a design rainfall. Marley Germany, for 300 l/(s·ha):
| Plan area per outlet | Gutter | Downpipe |
|---|---|---|
| up to 25 m² | RG 70 or RG 75 | DN 53 |
| up to 51 m² | RG 100 | DN 75 / DN 90 |
| up to 100 m² | RG 125 | DN 90 / DN 105 |
| up to 159 m² | RG 150 | DN 105 |
A second outlet halves the area each one drains, which often allows a smaller gutter. A 10 × 5 m roof face (50 m²) takes RG 100 with one outlet, or RG 75 with two.
Fragen
How many downspouts do I need?
Enough section for the roof area at your local rainfall, and at least one for every 50 ft of gutter.
Is a 2 × 3 downspout big enough?
Only for small areas such as porches. CDA asks for at least 7 sq in, and a 2 × 3 in downspout has 4.80 sq in inside.
Do I use the sloped roof area?
No. Use the plan area seen from above and multiply it by the pitch factor.
What gutter size for a 100 m² roof?
With Marley gutters at 300 l/(s·ha), RG 125 with one DN 90 or DN 105 outlet, or RG 100 with two outlets of 50 m² each.
Selbst rechnen
Dachrinnen-Rechner
Wie viele Fallrohre, welche Rinnengröße und wie viel Rohr für eine Dachseite nötig sind.
Dachrinnen-Rechner →Quellen
- [1]Copper in Architecture: 10.1 Hung Gutters and Downspouts Basics (Tables 10A, 10C). Copper Development Association. Area drained per square inch of downspout by city for 10-year and 100-year 5-minute storms (1,200 sq ft per sq in at 1 in/hr); plan area × pitch factor (level–3 in/ft 1.00, 4–5 1.05, 6–8 1.10, 9–11 1.20, 12 1.30); each downspout drains at most 50 ft of gutter; downspouts at least 7 sq in except small areas such as porches.. Geprüft am 10. November 2026
- [2]Gutter sizing (Table 1-3, downspout areas). GutterSupply. Actual cross-section of downspouts: 2×3 in plain rectangular 4.80 sq in (nominal 6.00), 3×4 in 10.31 (12.0), 3 in round 5.94 (7.07), 4 in round 11.04 (12.57).. Geprüft am 10. November 2026
- [3]Marley Dachrinnensysteme: Bemessungstabelle. Marley Deutschland. At a rainfall of 300 l/(s·ha): up to 25 m² roof plan area RG 70 or RG 75 with DN 53; up to 51 m² RG 100 with DN 75/90; up to 100 m² RG 125 with DN 90/105; up to 159 m² RG 150 with DN 105. Two outlets halve the area each one drains.. Geprüft am 10. November 2026