Heat loss calculator
Work out how much heat a room loses on the coldest day, through its walls, windows and roof and with the fresh air, and what radiator it needs at your water temperature.
Room
Simplified room heat load after DIN EN 12831: transmission U × A × ΔT plus air 0.34 Wh/(m³K) × air changes × volume × ΔT. No allowance for thermal bridges or reheating.
Size and temperatures
Minimum for living rooms 0.5, bathroom with window 1.5 (German National Annex).
20 °C for living rooms, 24 °C for bathrooms is the usual design value.
The coldest design temperature for your town, from the national annex of EN 12831 or your heating engineer.
Walls, windows, roof and floor
Only the surfaces that lose heat: outer walls, windows, roof, and walls or floors next to unheated rooms. Areas inside the room, without the window area in the wall.
Radiator
About 1.3 for panel radiators; the exact value is in the maker's table.
Radiators are sold by their output at 75/65/20 °C. The calculator converts the heat loss to that rating for your water temperatures.
Add this calculator to your website
Free for any website: paste this code where the calculator should appear. It keeps itself up to date, fits its height to the content and links back to the full page with the explanations.
使い方
- 01Pick the room type. It sets the usual room temperature and the minimum fresh air, which you can change.
- 02Enter the room size and the design outdoor temperature for your town.
- 03Add every surface that loses heat with its area and U-value: outer walls, windows, doors, roof, and floors or walls next to unheated rooms.
- 04Enter the flow and return temperature of your heating to see which radiator rating covers the room.
計算方法
A room loses heat in two ways: through the surfaces around it and with the air that is exchanged. Both grow with the difference between inside and outside on the coldest design day.
- Through a surface
- ΦT = A × U × (θi − θe)
- With the air
- ΦV = 0.34 × n × V × (θi − θe)
- Heat load
- Φ = ΣΦT + ΦV
- Radiator excess temperature
- Δθln = (θV − θR) / ln((θV − θi) / (θR − θi))
- Rating to buy
- Φ75/65/20 = Φ / (Δθln / 49.83)^n
The two heat loss formulas are those of DIN EN 12831 as explained in SBZ Monteur: 0.34 Wh/(m³K) is the heat that one cubic metre of air carries per kelvin. The German National Annex sets 20 °C for living rooms, 24 °C for bathrooms and a minimum of 0.5 air changes per hour in living rooms and 1.5 in a bathroom with a window.
In imperial units the air term is the same physics: 1.08 × cfm × ΔT in Btu/h (ACCA), with cfm = air changes × volume / 60.
Radiators are rated at 75 °C flow, 65 °C return and 20 °C room, an excess temperature of 49.83 K. At lower water temperatures they give less, by the ratio of excess temperatures to the power n, about 1.3 for panel radiators (Vogel & Noot lists 1.30 to 1.34).
This is the simplified room method. It leaves out thermal bridges, heat flow to heated neighbours and the detailed ground model, so a heating engineer’s full calculation can come out somewhat different.
計算例
Numbers from the SBZ examples
- A 10 m² outer wall with U = 1 W/(m²K), 20 °C inside and −10 °C outside: 10 × 1 × 30 = 300 W.
- A dining room of 39.52 m³ at 0.5 air changes: 19.76 m³/h × 0.34 × 34 K = 228 W at −14 °C outside.
- A radiator rated 627 W at 75/65/20 gives 594 W when the room is kept at 22 °C and about 561 W at 24 °C.
- A room that loses 1,000 W, heated with 55/45 °C water: factor 0.51, so a radiator rated about 1,960 W at 75/65/20.
発注時のポイント
Take U-values from your papers
The energy certificate, the window invoice or the insulation calculation lists the U-values. For a window use the value of the whole window, Uw, not of the glass alone.
Lower water temperature, bigger radiator
With a heat pump the water is often 35 to 55 °C. The radiator then gives a fraction of its rating, which is why old radiators are often too small after the switch.
Check the whole house too
Add up the rooms to compare with the boiler or heat pump size. The building total is usually smaller than the sum of rooms, because not every room needs its peak at the same time.
よくある間違い
- Counting the window area twice. Enter the wall area without the window, and the window as its own surface.
- Using a mild outdoor temperature. The design temperature is for the coldest days of the year, not the average winter day.
- Buying a radiator by its 75/65 rating for a heat pump. Convert to your flow and return temperature first.
- Forgetting walls to an unheated garage or cellar. They lose heat too, only less than outer walls.
よくある質問
How do I calculate the heat loss of a room?
Multiply each outer surface by its U-value and by the temperature difference between inside and outside, add the air term 0.34 × air changes × volume × temperature difference, and add everything up.
What size radiator do I need for a room?
Divide the room heat load by the share of the rating the radiator gives at your water temperatures. At 55/45 °C with a 20 °C room a panel radiator gives about half of its 75/65/20 rating.
What is the 75/65/20 rating?
The output a radiator gives with 75 °C flow, 65 °C return and a 20 °C room, the reference condition of EN 442. Makers list every radiator at this point.
What air change rate should I use?
The German National Annex sets at least 0.5 per hour for living rooms, 1.0 for an office and 1.5 for a bathroom with a window.
Where do I find the design outdoor temperature?
In Germany it is listed by town in the national annex of EN 12831; in the US the 99.6 % heating design temperature from ASHRAE climate data is used. Your heating engineer or local code office has the value.
このテーマのガイド
- Room heat loss and radiator size: a worked example
How to estimate the heat loss of a room through walls, windows and air (EN 12831 method), and how big a radiator to fit for low flow temperatures.
関連する計算ツール
出典
- [1]Heizlast-Berechnung nach DIN EN 12831, Teil 1 (E. Held, SBZ Monteur 01/2005). SBZ Monteur. ΦT = A × U × (θi − θe); ΦV = V̇ × 0.34 Wh/(m³K) × (θi − θe). Minimum air change 0.5 1/h for living rooms, 1.5 for a bathroom with window, 1.0 for an office; standard room temperatures 20 °C living, 24 °C bathroom, 15 °C heated corridors. Design outdoor temperature from the National Annex by place.. 確認日: 2026年11月11日
- [2]Auslegung von Heizkörpern (SBZ Monteur 2008, Heft 12). SBZ Monteur. Output at other temperatures from the norm output at 75/65/20 with the logarithmic mean excess temperature (49.83 K at norm) and the radiator exponent n ≈ 1.3. Check: type 10, 600 × 1000 mm, 627 W at 20 °C room, 594 W at 22 °C, 561 W at 24 °C.. 確認日: 2026年11月11日
- [3]Kompaktheizkörper, technische Informationen (gültig ab 1.3.2012). Vogel & Noot. Radiator exponent n for 600 mm panel radiators: type 10 1.301, type 11 1.319, type 21 1.310, type 22 1.343, type 33 1.333.. 確認日: 2026年11月11日
- [4]The Physics of Heat and Air Flow (A. Bailes III, 2018-05-02). ACCA HVAC Blog. Sensible heat of air: Btu/h = 1.08 × cfm × ΔT (0.075 lb/ft³ × 0.24 Btu/(lb·°F) × 60 min/h), near sea level and room temperature.. 確認日: 2026年11月11日
計算式と出典の最終確認日: 2026年11月11日。 計算方法